Maintenance Report

Search Filter:

Showing 15,001-15,010 of 17,159 items.

#DateTypeDetailsFurnaceEquipmentActions
1500125 Sep 2020Scheduled Maintenance1.check transformer temp. and oil level.it is ok. temp. is good.
2. check transformer oil leakage.no leakage.
3. check crystal color.it is ok..
Furnace IIFURNACE 2 TRANSFORMER NO. 2
1500225 Sep 2020Scheduled Maintenance1.check transformer temp. and oil level.it is ok.
2. check transformer oil leakage.no oil leakage.
3. check crystal color. its silica gel is not ok. we change it when its coming.
Furnace IFURNACE 1 TRANSFORMER
1500325 Sep 2020Scheduled Maintenance1.check solenoid valve condition and its pipe condition. it is ok. solenoid valves are in good condition.
2.check pneumatic cylinders and air supply lines.it is ok.
3. check charging chute leakage. if it is then inform HOD. small leakage we weld it on next shut down.
Furnace ICHARGING CHUTES
1500425 Sep 2020Scheduled Maintenance1.check solenoid valve condition and its pipe condition. it is ok. solenoid valves are in good condition.
2.check pneumatic cylinders and air supply lines.cylinder no. 3 repairing is done.
3. check to charge chute leakage. if it is then informed HOD. a small amount of leakage on the second floor we repaired it on the next shutdown.
Furnace IICHARGING CHUTES
1500525 Sep 2020Scheduled Maintenance1. checking loose parts and check the hydraulic oil level in the tank. we checked it and fill 20 ltr oil.
2. check solenoid valve working conditions and adjust oil pressure.it's ok.
3. check hydraulic line leakage. no leakage.
Furnace IHYDRAULIC POWER PACK NO. 1
1500625 Sep 2020Scheduled Maintenance1. checking loose parts and check the hydraulic oil level in the tank. we check it and fill 20 ltr oil.
2. check solenoid valve working conditions and adjust oil pressure.it's ok.
3. check hydraulic line leakage.no leakage.
Furnace IIHYDRAULIC POWER PACK NO. 2
1500725 Sep 2020Scheduled Maintenance1. check the water manifold line, T section, and valves. checked. no leakage.
2. check leakage of hose pipes.its ok.
Furnace IWATER MAINEFOLD
1500825 Sep 2020Scheduled Maintenance1. check the water manifold line, T section, and valves. one valve has a small amount of leakage. we repaired it on the next shutdown.
2. check leakage of hose pipes.its ok.
Furnace IIWATER MAINEFOLD
1500925 Sep 2020Scheduled Maintenance1. by air pipe clean dust from all cylinders.clean and small amount of fire coming top side from the seal.
2. check leakage of hydraulic oil. if it is then informed to HOD.its ok.
Furnace IELECTRODE 2
1501025 Sep 2020Scheduled Maintenance1. by air pipe clean dust from all cylinders. clean but seal side fire coming. we mount rope but it's not good.
2. check leakage of hydraulic oil. if it is then informed to HOD. slipping cylinder side a small amount of leakage is there we tight it on next shutdown.
Furnace IELECTRODE 3